With over 10,000 orders
Water Leakage Detector System protects facilities such as computer rooms, critical facilities, warehouses, and critical document rooms from water leaks and flooding accidents. The System is composed of at least one line type sensor that quickly detects water leaks along with a water leakage detector that alerts the water leaks to the user in a timely manner.
Water leak location is electronically measured and digitally displayed at units of 1 meter. Furthermore, when a water leak occurs, the sensor uses a colored display, making an on-site visual confirmation easy and making it possible to identify the location of the leak more quickly.
We offers the following water leakage detector & sensors as standard set, which are in control of one circuits according to the user's requirement. Each model incorporates a non-voltage output terminal that can be connected to a central monitoring panel.
Product Specification//
There are 3 Components inside the package.
- Detector
TATSUTA AD-AS-1DM detector can be mounted to the DIN track in the panel and connected with DC power.
Model |
TATSUTA AD-AS-1DM |
Number of sensor circuits |
1 circuit |
Rated Voltage |
AC24V±10%(for 50Hz/60Hz) DC24V±10% |
Voltage across sensor |
AC5.3V |
Water leakage alarm indicator |
Orange LED flash |
Break alarm indicator |
Orange LED flash |
Control output Contacts |
AC125V 0.2A DC30V 1.0A |
Power Consumption |
3W max. |
Set sensitivity |
4 level |
Outside dimensions W×H×D(mm) |
22×28×59 |
Weight(kg) |
0.059 |
- Sensor
TATSUTA AD-S Sensor is the non-coloring water leakage sensor which promptly detects any water leak.
Model |
TATSUTA AD-S Sensor (Non-coloration model) |
Construction |
Material: Strand of tinned annealed copper wires Composition: Copper wire 0.18 mm in diameter × 13 (0.33 mm2 ) |
Electrode resistance(DC)
|
Standard: 26.6 Ω/km (20°C) |
Resistance between electrodes(AC) |
50kΩmin. |
Insulation performance |
Insulation resistance between electrodes is 10 MΩ min. when measured with a 100 VDC Insulation Tester. |
Sensitivity (Water absorptivity) |
Resistance between electrodes is 5 kΩ max. when water absorption is 3.0 ml or less. (Tap water is allowed to drop at a rate of 0.05 ml/s directly on the sensor.) |
Moisture resistance between electrodes |
Resistance between electrodes is 50 kΩ min. even in a highly humid environment but without dew condensation. |
Reusability |
After leakage detection, the sensor is reset and can be reused within 30 min if it is retained under normal conditions (i.e., not exposed to water). The sensor cannot be reused if it has absorbed water that contains conductive or water-repellent material. |
Heat resistance |
60°C max. for continuous operation. |
Radiation resistance |
No performance deterioration (water absorptivity, moisture resistance, and mechanical properties) results after exposure to 50 Mrad(Note) . |
Weight |
10.5±1.0 g/m |
Length |
10m |
(Note) Estimated quantity of radiation to which electric cables can be exposed Over the period of 40 years, which is the designed service life of a typical nuclear power plant.
- Wire Disconnection Detection Terminal
This is a sensor terminal used for on-site installation.
Model |
TATSUTA ZT-2 |
Number |
1 |
Item Specification
|
Use parts: 1-Lead Wire: PVC UL1015LF 22AWG WHITE 2-Resistor: 20kΩ±2% 1/4W metal film resistor 3-Solder: Pb-free solder 4-Cap: PVC tube 5-Filling thing: Silicone rubber |
Resistance between electrodes (AC) |
20kΩ±1% |
Moisture resistivity
|
Resistance between electrodes is 20kΩ±10% under heavy wet condition, expecting dew condensing environment. |
Heat resistivity |
60 max. for continuous operation. |
Weight: |
3.2g±0.8g |